Mechanical ventilation design in Australia starts with AS 1668.2. Before ducts are sized or fans are selected, a building services engineer has to establish how much outdoor air each enclosure needs and, for an enclosed car park, how much exhaust air the system must move. This free ventilation calculator, built for use with AS 1668.2 rates, turns that first-pass arithmetic into a structured, documented worksheet.
The calculator deliberately contains no hidden tables. Instead, you enter each rate and factor from the governing standard or your project design basis, and the tool does the arithmetic transparently. For outdoor air, it multiplies the design occupancy by your per-person rate, adds an area-based component only where you enter one, and reports airflow in L/s, m³/h and CFM, along with air changes per hour and a CO₂ indicator. For enclosed car parks, it compares the exhaust criteria you enter and estimates fan electrical input power. When you finish, you can export a printable summary or a CSV file for your project records.
Because every rate is user-entered, engineers outside Australia can also use the outdoor air module with rates from ASHRAE 62.1 or another local standard. Where a simple calculation cannot show how air actually moves through a car park, a plant room or an atrium, CFD analysis services take over.
Quick answer
Outdoor airflow for an enclosure: Q = N × Rp, where N is the design number of occupants and Rp the outdoor air rate per person required for that space. Add an area component, A × Ra, only where your governing requirement specifies one. For enclosed car parks, the calculator compares the exhaust criteria you enter and reports the largest.
Take every rate, factor and procedure from the current edition of AS 1668.2 or your project design basis. The calculator performs the arithmetic but does not decide which requirements apply.

AS 1668.2 Ventilation Calculator
Build a room-by-room outdoor air schedule or compare enclosed car park exhaust criteria, then export a design summary. The calculator does the arithmetic only: you enter every rate and factor from AS 1668.2, another governing standard or your project design basis. Preloaded values are illustrative examples, not quoted from any standard.
Project and CO₂ Assumptions
Enclosures
Enter the occupants directly, or leave occupants blank and give a design density in m² per person. Enter the outdoor air rate per person from your governing requirement. Leave the area rate at 0 unless that requirement specifies an area-based component. Supply airflow is optional; enter it for every room to run the critical enclosure diagnostic.
Outdoor Air Results
| Enclosure | People | People OA (L/s) | Area OA (L/s) | Outdoor air (L/s) | m³/h | L/s·m² | OA ACH | CO₂ indicator (ppm) | OA / supply |
|---|
Car Park Geometry
Airflow Criteria
Enter the criteria, rates and any factor defined by your governing standard for this car park. Confirm first which procedure applies: simplified procedures are usually limited in scope, and larger or more complex car parks may need a detailed procedure. The example values are illustrative only and are not quoted from AS 1668.2. Leave a criterion at 0 if it does not apply.